No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-01

(0321)

Motor 2 Rated Current

Sets the motor rated current for motor 2 in amps.

Determined by o2-04, C6-01

(10% to 200% of the drive rated current)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-02

(0322)

Motor 2 Rated Slip

Sets the motor rated slip for motor 2.

Determined by o2-04, C6-01

(0.000 - 20.000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-03

(0323)

Motor 2 Rated No-Load Current

Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load voltage.

Determined by o2-04, C6-01

(Less than 0 - E4-01)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-04

(0324)

Motor 2 Motor Poles

Sets the number of poles for motor 2.

4

(2 - 120)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-05

(0325)

Motor 2 Line-to-Line Resistance

Sets the line-to-line resistance for the motor 2 stator windings.

Note:

On drive models 4810 to 4H12, the unit is mΩ, and the setting range is 0.000 mΩ to 65.000 mΩ.

Determined by o2-04, C6-01

(0.000 - 65.000 Ω)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-06

(0326)

Motor 2 Leakage Inductance

Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage when motor 2 operates at the rated frequency and rated current.

Determined by o2-04, C6-01

(0.0 - 60.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-07

(0343)

Motor 2 Saturation Coefficient 1

Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux.

0.50

(0.00 - 0.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-08

(0344)

Motor 2 Saturation Coefficient 2

Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux.

0.75

(E4-07 - 0.75)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-09

(033F)

Expert

Motor 2 Mechanical Loss

Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [Motor 2 Rated Power]. Usually it is not necessary to change this setting.

0.0%

(0.0 - 10.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-10

(0340)

Motor 2 Iron Loss

Sets the motor iron loss for motor 2.

Determined by o2-04, C6-01

(0 - 65535 W)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E4-11

(0327)

Motor 2 Rated Power

Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].

Note:

On drive models 2xxx, and 4002 to 4675, the setting unit is 0.01 kW. The setting range is 0.00 kW to 650.00 kW (0.00 HP to 650.00 HP).

On drive models 4810 to 4H12, the setting unit is 0.1 kW. The setting range is 0.0 kW to 1000.0 kW (0.0 HP to 1340.5 HP).

Determined by o2-04, C6-01

(0.00 - 1000.0)

Details