No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-01

(042C)

Terminal RP Pulse Train Function

Sets the function for pulse train input terminal RP.

0
Frequency Reference

When b1-01 = 4 [Frequency Reference Selection 1 = Pulse Train Input] or b1-15 = 4 [Frequency Reference Selection 2 = Pulse Train Input], the drive inputs the frequency reference received from terminal RP.

1
PID Feedback Value

The drive inputs the PID control feedback value received from terminal RP.

2
PID Setpoint Value

The drive inputs the PID control target value received from terminal RP.

3
Speed Feedback (V/F Control)

Select V/f Control method to enable simple encoder feedback.

0

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-02

(042D)

RUN

Terminal RP Frequency Scaling

Sets the frequency of the pulse train input signal used when the item selected with H6-01 [Terminal RP Pulse Train Function] is input at 100%.

1440 Hz

(100 - 32000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-03

(042E)

RUN

Terminal RP Function Gain

Sets the gain used when the function in H6-01 [Terminal RP Pulse Train Function] is input to terminal RP.

100.0%

(0.0 - 1000.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-04

(042F)

RUN

Terminal RP Function Bias

Sets the bias used when the function in H6-01 [Terminal RP Pulse Train Function] is input to terminal RP. Sets a value at the time when the pulse train is 0 Hz.

0.0%

(-100.0 - 100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-05

(0430)

RUN

Terminal RP Filter Time

Sets the time constant for the pulse train input primary delay filters.

0.10 s

(0.00 - 2.00 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-06

(0431)

RUN

Terminal MP Monitor Selection

Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx monitor.

102

(000, 031, 101, 102, 105, 116, 501, 502, 801 - 809, 821 - 825, 831 - 839, 851 - 855)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-07

(0432)

RUN

Terminal MP Frequency Scaling

Sets the frequency of the pulse train output signal used when the monitor set with H6-06 [Terminal MP Monitor Selection] is 100%.

1440 Hz

(0 - 32000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-08

(043F)

Terminal RP Minimum Frequency

Sets the minimum frequency of the pulse train signal that terminal RP can detect.

0.5 Hz

(0.1 - 1000.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-09

(156E)

Voltage Phase Sync MP Selection

Set whether to output the pulse synchronized with drive output voltage phase from the pulse train monitor output terminal MP. This parameter is only enabled when H6-06 = 102 [Terminal MP Monitor Selection = Output Frequency] and H6-07 = 0 [Terminal MP Frequency Scaling = 0 Hz].

0
Disabled
 
1
Enabled
 

0

(0, 1)

Details