No.

(Hex.)

Name

Description

MFAO Signal Level

U5-01

(0057)

PID Feedback

Shows the PID control feedback value. Parameter b5-20 [PID Unit Selection] sets the display units.

0.01%

10 V: Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-02

(0063)

PID Input

Shows the change between the PID setpoint and PID feedback (the quantity of PID input) as a percentage of the maximum output frequency.

0.01%

10 V: Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-03

(0064)

PID Output

Shows the PID control output as a percentage of the maximum output frequency.

0.01%

10 V: Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-04

(0065)

PID Setpoint

Shows the PID setpoint. Parameter b5-20 [PID Unit Selection] sets the display units.

0.01%

10 V: Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-05

(07D2)

PID DifferentialFdbk

Shows the PID differential feedback value as a percentage of the maximum output frequency.

This monitor is available after you set H3-02, H3-10, or H3-06 = 16 [MFAI Function Selection = Differential PID Feedback].

0.01%

10 V = Maximum frequency (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-06

(07D3)

PID Fdbk-Diff PID Fdbk

Shows the difference from calculating U5-05 - U5-01 [PID DifferentialFdbk] - [PID Feedback].

0.01%

Note:

U5-01 [PID Feedback] = U5-06 when H3-02, H3-10, or H3-06 ≠ 16 [MFAI Function Selection ≠ Differential PID Feedback].

10 V = Maximum frequency (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-21

(0872)

Expert

Energy Save Coeff Ki

Shows the energy-saving coefficient Ki value for PM.

0.01

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-22

(0873)

Expert

Energy Save Coeff Kt

Shows the energy-saving coefficient Kt value for PM.

0.01

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U5-99

(1599)

PID Setpoint Command

Shows the PID setpoint command. Parameter b5-20 [PID Unit Selection] sets the display units.

0.01%

10 V: Maximum frequency (0 V to +10 V)