Jump to main content

o5: Log Function

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-00

(1E81)

RUN

Log Type

Sets the type of data log function. This parameter is only available when you use an LCD keypad.

0
Long Term Log

Saves data continuously over a long time period.

1
Short Term Log

Saves data over a set length of time before and after the drive detects a trigger event with a short sampling cycle.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-01

(1551)

RUN

Log Start/Stop Selection

Sets the data log function. This parameter is only available when using an LCD keypad.

0
OFF

Stops the data log.

1
ON

Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].

0

(0 - 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-02

(1552)

RUN

Log Sampling Interval

Sets the data log sampling cycle. This parameter is only available when you use an LCD keypad.

Note:

The default setting and setting range change when o5-00 [Normal / Heavy Duty Selection] changes.

  • o5-00 = 0 [Long Term Log]

    • Default setting: 1000 ms

    • Setting range: 100 - 60000 ms

  • o5-00 = 1 [Short Term Log]

    • Default setting: 10 ms

    • Setting range: 1 - 99 ms

Determined by o5-00

(Determined by o5-00)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-03

(1553)

RUN

Log Monitor Data 1

Sets the data log monitor. This parameter is only available with an LCD keypad.

101

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-04

(1554)

RUN

Log Monitor Data 2

Sets the data log monitor (Ux-xx). This parameter is only available when you use an LCD keypad.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set o5-04 = 102 to monitor U1-02 [Output Frequency].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set o5-04 = 1301 to monitor Ud-01.

102

(000, 101 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-05

(1555)

RUN

Log Monitor Data 3

Sets the data log monitor. This parameter is only available with an LCD keypad.

103

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-06

(1556)

RUN

Log Monitor Data 4

Sets the data log monitor. This parameter is only available with an LCD keypad.

107

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-07

(1557)

RUN

Log Monitor Data 5

Sets the data log monitor. This parameter is only available with an LCD keypad.

108

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-08

(1558)

RUN

Log Monitor Data 6

Sets the data log monitor (Ux-xx). This parameter is only available when you use an LCD keypad.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set o5-08 = 101 to monitor U1-01 [Frequency Reference].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set o5-08 = 1301 to monitor Ud-01.

000

(000, 101 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-09

(1559)

RUN

Log Monitor Data 7

Sets the data log monitor (Ux-xx). This parameter is only available when you use an LCD keypad.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set o5-09 = 101 to monitor U1-01 [Frequency Reference].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set o5-09 = 1301 to monitor Ud-01.

000

(000, 101 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-10

(155A)

RUN

Log Monitor Data 8

Sets the data log monitor. This parameter is only available with an LCD keypad.

000

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-11

(155B)

RUN

Log Monitor Data 9

Sets the data log monitor. This parameter is only available with an LCD keypad.

000

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-12

(155C)

RUN

Log Monitor Data 10

Sets the data log monitor. This parameter is only available with an LCD keypad.

000

(000, 101 - 999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-15

(1E82)

RUN

Trigger Type Selection

Sets the type of trigger for the short-term data log. This parameter is only available when you use an LCD keypad.

0
Digital Trigger

A digital signal inside the drive will act as the trigger.

1
Analog Trigger

An analog signal inside the drive will act as the trigger.

Note:

There are no detection width and detection time settings for the analog trigger in the data log function. If variations in the analog signal are a problem, set o5-15 = 0 and o5-16 = 66, 67 [Digital Trigger Object = Comparator 1, 2]. Use H2-20 [Comparator 1 Monitor Selection] to H2-32 [Comparator 1 Filter Time] to set the conditions for the comparator function.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-16

(1E83)

RUN

Digital Trigger Object

Sets the function for the digital trigger target from the setting values for multi-function digital outputs. This parameter is only available when you use an LCD keypad.

E

(0 - FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-17

(1E84)

RUN

Analog Trigger Object

Sets the monitor for the analog trigger target. This parameter is only available when you use an LCD keypad.

Note:
  • Set the x-xx part of the Ux-xx [Monitor]. For example, set o5-17 = 101 to monitor U1-01 [Frequency Reference].

    When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set o5-17 = 1301 to monitor Ud-01.

  • When it is not necessary to set a data log monitor, set this parameter to 000.

102

(0 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-18

(1E85)

RUN

Analog Trigger Level

Sets the level to compare with the analog trigger target. This parameter is only available when you use an LCD keypad.

0.0%

(-999.9% - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-19

(1E86)

RUN

Trigger Condition

Sets the condition with which to detect the trigger. This parameter is only available when you use an LCD keypad.

0
Rising Edge
  • Digital trigger: The drive detects the trigger when the digital trigger target switches from OFF to ON.

  • Analog trigger: The drive detects the trigger when the analog trigger target changes from “less than” to “equal or more than” the trigger level set in o5-18 [Analog Trigger Level].

1
Falling Edge
  • Digital trigger: The drive detects the trigger when the digital trigger target switches from ON to OFF

  • Analog trigger: The drive detects the trigger when the analog trigger target changes from “equal to or more than” to “less than” the trigger level set in o5-18.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-20

(1E87)

RUN

Pre-Trigger Setting

Sets the percentage of data to save before the drive detects the trigger for the short-term data log. This parameter is only available when you use an LCD keypad.

90%

(0% - 100%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o5-21

(1E88)

RUN

Trend Log Sampling Time Selection

Sets the sampling cycle for the trend log to save data before the drive detects the trigger. The trend log works at the same time as the short-term data log. This parameter is only available when you use an LCD keypad.

0
Trend Log Disabled

The drive does not save the trend log.

1
0.1 s (About 1 hour)

Saves a trend log with a sampling cycle of 0.1 s. The drive saves a maximum of approximately one hour of data before it detects the trigger.

2
1 s (About 10 hours)

Saves a trend log with a sampling cycle of 1 s. The drive saves a maximum of approximately 10 hours of data before it detects the trigger.

3
10 s (About 100 hours)

Saves a trend log with a sampling cycle of 10 s. The drive saves a maximum of approximately 100 hours of data before it detects the trigger.

4
60 s (About 600 hours)

Saves a trend log with a sampling cycle of 60 s. The drive saves a maximum of approximately 600 hours of data before it detects the trigger.

0

(0 - 4)

Details