No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-01

(0499)

Speed Agree Detection Level

Sets the level to detect speed agree or motor speed when H2-01 to H2-04 = 2, 3, 4, 5 [MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].

Determined by A1-02

(Determined by A1-02)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-02

(049A)

Speed Agree Detection Width

Sets the width to detect speed agree or motor speed.

Sets the width to detect speed agree or motor speed when H2-01 to H2-04 = 2, 3, 4, 5 [MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].

Determined by A1-02

(Determined by A1-02)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-03

(049B)

Speed Agree Detection Level (+/-)

Sets the level to detect speed agree or motor speed.

Sets the level to detect speed agree or motor speed when H2-01 to H2-04 = 13, 14, 15, 16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4].

Determined by A1-02

(Determined by A1-02)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-04

(049C)

Speed Agree Detection Width (+/-)

Sets the width to detect speed agree or motor speed.

Sets the width to detect speed agree or motor speed when H2-01 to H2-04 = 13, 14, 15, 16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4].

Determined by A1-02

(Determined by A1-02)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-05

(049D)

Fref Loss Detection Selection

Sets the operation when the drive detects a loss of frequency reference.

0
Stop
 
1
Run at (L4-06 x Last Reference)
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-06

(04C2)

Frequency Reference @Loss of Ref

Sets the frequency reference as a percentage to continue drive operation after it detects a frequency reference loss. The value is a percentage of the frequency reference before the drive detected the loss.

80.0%

(0.0 - 100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L4-07

(0470)

Speed Agree Detection Selection

Sets the condition that activates speed detection.

0
No Detection during Baseblock
 
1
Detection Always Enabled
 

0

(0, 1)

Details