No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d7-01

(02B2)

RUN

Offset Frequency 1

Uses H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a percentage of the Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

0.0%

(-100.0 - +100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d7-02

(02B3)

RUN

Offset Frequency 2

Uses H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a percentage of the Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

0.0%

(-100.0 - +100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d7-03

(02B4)

RUN

Offset Frequency 3

Uses H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a percentage of the Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

0.0%

(-100.0 - +100.0%)

Details