No. (Hex.) Name Description Default (Range) Ref. H5-01 (0425) Drive Node Address Sets the communication slave address for drives. Note: Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting. Setting 0 will not let the drive respond to MEMOBUS/Modbus communications. 1FH (0 - FFH) Details No. (Hex.) Name Description Default (Range) Ref. H5-02 (0426) Communication Speed Selection Sets the communications speed for MEMOBUS/Modbus communications. Note: Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting. 0 1200 bps 1 2400 bps 2 4800 bps 3 9600 bps 4 19.2 kbps 5 38.4 kbps 6 57.6 kbps 7 76.8 kbps 8 115.2 kbps 3 (0 - 8) Details No. (Hex.) Name Description Default (Range) Ref. H5-03 (0427) Communication Parity Selection Sets the communications parity used for MEMOBUS/Modbus communications. Note: Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting. 0 No parity 1 Even parity 2 Odd parity 0 (0 - 2) Details No. (Hex.) Name Description Default (Range) Ref. H5-04 (0428) Communication Error Stop Method Sets the motor Stopping Method when the drive detects CE [Modbus Communication Error] issues. 0 Ramp to Stop 1 Coast to Stop 2 Fast Stop (Use C1-09) 3 Alarm Only 3 (0 - 3) Details No. (Hex.) Name Description Default (Range) Ref. H5-05 (0429) Comm Fault Detection Selection Sets the function that detects CE [Modbus Communication Error] issues during MEMOBUS/Modbus communications. 0 Disabled 1 Enabled 1 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-06 (042A) Drive Transmit Wait Time Sets the time to wait to send a response message after the drive receives a command message from the master. Note: Restart the drive after changing the parameter setting. 5 ms (0 - 65 ms) Details No. (Hex.) Name Description Default (Range) Ref. H5-09 (0435) CE Detection Time Sets the detection time for CE [Modbus Communication Error] issues when communication stops. 2.0 s (0.0 - 10.0 s) Details No. (Hex.) Name Description Default (Range) Ref. H5-10 (0436) Modbus Register 0025H Unit Sel Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H (output voltage reference monitor). 0 0.1 V units 1 1 V units 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-11 (043C) Comm ENTER Command Mode Sets the function to make the Enter command necessary to change parameters through MEMOBUS/Modbus communications. 0 ENTER Command Required 1 ENTER Command Not Required 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-12 (043D) Run Command Method Selection Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 = Memobus/Modbus Communications] or b1-16 = 2 [Run Command Selection 2 = Memobus/Modbus Communications]. 0 FWD/Stop, REV/Stop 1 Run/Stop, FWD/REV 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-17 (11A1) Expert ENTER command response @CPU BUSY Sets operation when the EEPROM write command is sent without EEPROM write available. Usually it is not necessary to change this setting. 0 Ignore Command(No ROM/RAM Write) 1 Write to RAM Only 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-18 (11A2) Motor Speed Filter over Comms Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus communications or with a communication option. 0 ms (0 - 100 ms) Details No. (Hex.) Name Description Default (Range) Ref. H5-20 (0B57) Communication Parameters Reload Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters. 0 Reload at Next Power Cycle 1 Reload Now 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-22 (11CF) Speed Search from MODBUS Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH). 0 Disabled 1 Enabled 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H5-25 (1589) RUN Function 5A Register 1 Selection Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device. 0044H (U1-05) (0000H - FFFFH) Details No. (Hex.) Name Description Default (Range) Ref. H5-26 (158A) RUN Function 5A Register 2 Selection Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device. 0045H (U1-06) (0000H - FFFFH) Details No. (Hex.) Name Description Default (Range) Ref. H5-27 (158B) RUN Function 5A Register 3 Selection Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device. 0042H (U1-03) (0000H - FFFFH) Details No. (Hex.) Name Description Default (Range) Ref. H5-28 (158C) RUN Function 5A Register 4 Selection Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device. 0049H (U1-10) (0000H - FFFFH) Details