No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-01

(0425)

Drive Node Address

Sets the communication slave address for drives.

Note:
  • Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting.

  • Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.

1FH

(0 - FFH)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-02

(0426)

Communication Speed Selection

Sets the communications speed for MEMOBUS/Modbus communications.

Note:

Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting.

0
1200 bps
 
1
2400 bps
 
2
4800 bps
 
3
9600 bps
 
4
19.2 kbps
 
5
38.4 kbps
 
6
57.6 kbps
 
7
76.8 kbps
 
8
115.2 kbps
 

3

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-03

(0427)

Communication Parity Selection

Sets the communications parity used for MEMOBUS/Modbus communications.

Note:

Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after you change the parameter setting.

0
No parity
 
1
Even parity
 
2
Odd parity
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-04

(0428)

Communication Error Stop Method

Sets the motor Stopping Method when the drive detects CE [Modbus Communication Error] issues.

0
Ramp to Stop
 
1
Coast to Stop
 
2
Fast Stop (Use C1-09)
 
3
Alarm Only
 

3

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-05

(0429)

Comm Fault Detection Selection

Sets the function that detects CE [Modbus Communication Error] issues during MEMOBUS/Modbus communications.

0
Disabled
 
1
Enabled
 

1

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-06

(042A)

Drive Transmit Wait Time

Sets the time to wait to send a response message after the drive receives a command message from the master.

Note:

Restart the drive after changing the parameter setting.

5 ms

(0 - 65 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-09

(0435)

CE Detection Time

Sets the detection time for CE [Modbus Communication Error] issues when communication stops.

2.0 s

(0.0 - 10.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-10

(0436)

Modbus Register 0025H Unit Sel

Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H (output voltage reference monitor).

0
0.1 V units
 
1
1 V units
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-11

(043C)

Comm ENTER Command Mode

Sets the function to make the Enter command necessary to change parameters through MEMOBUS/Modbus communications.

0
ENTER Command Required
 
1
ENTER Command Not Required
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-12

(043D)

Run Command Method Selection

Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 = Memobus/Modbus Communications] or b1-16 = 2 [Run Command Selection 2 = Memobus/Modbus Communications].

0
FWD/Stop, REV/Stop
 
1
Run/Stop, FWD/REV
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-17

(11A1)

Expert

ENTER command response @CPU BUSY

Sets operation when the EEPROM write command is sent without EEPROM write available. Usually it is not necessary to change this setting.

0
Ignore Command(No ROM/RAM Write)
 
1
Write to RAM Only
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-18

(11A2)

Motor Speed Filter over Comms

Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus communications or with a communication option.

0 ms

(0 - 100 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-20

(0B57)

Communication Parameters Reload

Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.

0
Reload at Next Power Cycle
 
1
Reload Now
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-22

(11CF)

Speed Search from MODBUS

Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH).

0
Disabled
 
1
Enabled
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-25

(1589)

RUN

Function 5A Register 1 Selection

Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device.

0044H (U1-05)

(0000H - FFFFH)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-26

(158A)

RUN

Function 5A Register 2 Selection

Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device.

0045H (U1-06)

(0000H - FFFFH)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-27

(158B)

RUN

Function 5A Register 3 Selection

Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device.

0042H (U1-03)

(0000H - FFFFH)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H5-28

(158C)

RUN

Function 5A Register 4 Selection

Returns the contents of the specified MEMOBUS/Modbus communications register when responding to the master device.

0049H (U1-10)

(0000H - FFFFH)

Details