No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-01

(0580)

Hunting Prevention Selection

Sets the function to prevent hunting.

0
Disabled
 
1
Enabled (Normal)
 
2
Enabled (High Carrier Frequency)
 

Determined by o2-04

(0 to 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-02

(0581)

Expert

Hunting Prevention Gain Setting

Sets the performance of the hunting prevention function. Usually it is not necessary to change this parameter.

1.00

(0.00 - 2.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-03

(0582)

Expert

Hunting Prevention Time Constant

Sets the primary delay time constant of the hunting prevention function. Usually it is not necessary to change this parameter.

Determined by o2-04

(0 - 500 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-05

(0530)

Expert

Hunting Prevent Gain in Reverse

Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually it is not necessary to change this parameter.

0.00

(0.00 - 2.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-08

(1105)

Expert

Current Detection Method

Sets how the drive decreases the motor vibration that is caused by leakage current. Usually it is not necessary to change this parameter.

0
2-Phases
 
1
3-Phases
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-13

(1B59)

Expert

DC Bus Stabilization Control

Sets the oscillation suppression function for the DC bus voltage.

0
Disabled
 
1
Enabled
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-14

(1B5A)

Expert

DC Bus Stabilization Time

Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage. Set n1-13 = 1 [DC Bus Stabilization Control = Enabled] to enable this parameter.

100.0 ms

(50.0 - 500.0 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-15

(0BF8)

Expert

PWM Voltage Offset Calibration

Sets the calibration method that the drive uses to decrease torque/current ripple.

0
No Calibration
 
1
One Time Calibrate at Next Start
 
2
Calibrate Every Time at Start
 

Determined by A1-02

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-16

(0BFB)

Hunting Prevention High Fc Gain

Sets the gain for the hunting prevention function. This parameter functions best with a high carrier frequency. Usually it is not necessary to change this parameter.

Determined by o2-04

(0.00 - 2.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-17

(0BFC)

Expert

Hunting Prevent High Fc Filter

Sets the responsiveness of the hunting prevention function. Usually it is not necessary to change this parameter.

500 ms

(0 - 1000 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n1-20

(1588)

Expert

Voltage Calibration Duration

Sets the calibration time at start. Usually it is not necessary to change this parameter.

50 ms

(10 - 500 ms)

Details