Stopping Method Selection
|
       
Sets the method to stop the motor after removing a Run command or entering a Stop command.
Note:
When A1-02 = 3, 4, 5, 6, 7, 8 [Control Method Selection = CLV, AOLV, OLV/PM, AOLV/PM, CLV/PM, EZOLV], the setting range is 0, 1, 3.
- 0
- Ramp to Stop
-
When you enter the Stop command or turn OFF the Run command, the drive ramps the motor to stop.
- 1
- Coast to Stop
-
When you enter the Stop command or turn OFF the Run command, the drive turns OFF the output and coasts the motor to stop.
- 2
- DC Injection Braking to Stop
-
When you enter the Stop command or turn OFF or Run command, the drive turns OFF the output for the time set in L2-03. The drive waits for the minimum baseblock time and then injects the amount of DC current into the motor set in b2-02 [DC Injection Braking Current] to stop the motor with DC current.
Note:
If A1-02 = 3, 4, 5, 6, or 7, DC Injection Braking to Stop is not available.
- 3
- Coast to Stop with Timer
-
When you enter the Stop command or turn OFF the Run command, the drive turns OFF the output and coasts the motor to stop. The drive ignores the Run command until the “Run wait time t” is expired.
|