Jump to main content

C1: Accel & Decel Time

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-01

(0200)

RUN

Acceleration Time 1

Sets the length of time to accelerate from zero to maximum output frequency.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-02

(0201)

RUN

Deceleration Time 1

Sets the length of time to decelerate from maximum output frequency to zero.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-03

(0202)

RUN

Acceleration Time 2

Sets the length of time to accelerate from zero to maximum output frequency.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-04

(0203)

RUN

Deceleration Time 2

Sets the length of time to decelerate from maximum output frequency to zero.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-05

(0204)

RUN

Acceleration Time 3

Sets the length of time to accelerate from zero to maximum output frequency.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-06

(0205)

RUN

Deceleration Time 3

Sets the length of time to decelerate from maximum output frequency to zero.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-07

(0206)

RUN

Acceleration Time 4

Sets the length of time to accelerate from zero to maximum output frequency.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-08

(0207)

RUN

Deceleration Time 4

Sets the length of time to decelerate from maximum output frequency to zero.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-09

(0208)

RUN

Fast Stop Time

Sets the length of time that the drive will decelerate to zero for a Fast Stop.

Note:
  • Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the drive while the motor to coasts to a stop. Set a Fast Stop time in C1-09 that prevents motor coasting and makes sure that the motor stops quickly and safely.

  • When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1] and you do KEB Auto-Tuning, the drive will automatically set C1-09. If you must not change the Fast Stop time, do not do KEB Tuning.

10.0 s

(0.0 - 6000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-10

(0209)

Accel/Decel Time Setting Units

Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop Time], L2-06 [Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup Accel Time].

0
0.01 s (0.00 to 600.00 s)

Sets acceleration and deceleration times in 0.01 s units. The setting range is 0.00 to 600.00 s.

1
0.1 s (0.0 to 6000.0 s)

Sets acceleration and deceleration times in 0.1 s units. The setting range is 0.0 to 6000.0 s.

1

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-11

(020A)

Accel/Decel Time Switching Frequency

Sets the frequency at which the drive will automatically change acceleration and deceleration times.

Determined by A1-02

(0.0 - 590.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C1-14

(0264)

RUN

Accel/Decel Rate Frequency

Sets the base frequency used to calculate acceleration and deceleration rates.

0.0 Hz

(0.0 - 590.0 Hz)

Details