U1: Operation Status Monitors

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-01

(0040)

Frequency Reference

Shows the frequency reference value. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.

0.01 Hz

10 V = Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-02

(0041)

Output frequency

Shows the output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.

0.01 Hz

10 V = Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-03

(0042)

Output current

Shows the output current.

The keypad shows the value of U1-03 in amperes (A). When you use MEMOBUS/Modbus communications to show the monitor, the current is “8192 = drive rated current (A)”. Use the formula: “Numerals being displayed / 8192 × drive rated current (A)” to use the MEMOBUS/Modbus communication current value shown in the monitor.

When the drive model changes, the display units for this parameter also change.

  • 0.01 A: 2004 - 2042, 4002 - 4023

  • 0.1 A: 2056 - 2415, 4031 - 4675

  • 1 A: 4810 - 4H12

10 V = Drive rated current

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-04

(0043)

Control Method

Shows the drive control method.

0
V/f Control
 
1
V/f Control with Encoder
 
2
Open Loop Vector
 
3
Closed Loop Vector
 
4
Advanced Open Loop Vector
 
5
PM Open Loop Vector
 
6
PM Advanced Open Loop Vector
 
7
PM Closed Loop Vector
 
8
EZ Vector Control
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-05

(0044)

Motor Speed

Shows the detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.

0.01 Hz

10 V = Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-06

(0045)

Output Voltage Ref

Shows the output voltage reference.

0.1 V

200 V Class: 10 V = 200 Vrms

400 V Class: 10 V = 400 Vrms

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-07

(0046)

DC Bus Voltage

Shows the DC bus voltage.

1 V

200 V Class: 10 V = 400 V

400 V Class: 10 V = 800 V

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-08

(0047)

Output Power

Shows the internally-calculated output power.

When you change A1-02 [Control Method Selection], it will also change the signal level of the analog output.

  • A1-02 = 0, 1: Drive capacity (kW)

  • A1-02 = 2, 3, 4: PM Motor Rated Power [E2-11] (kW)

  • A1-02 = 5, 6, 7: PM Motor Rated Power [E5-02] (kW)

  • A1-02 = 8: Motor Rated Power [E9-07] (kW)

The display units are different for different models:

  • 0.01 kW: 2004 - 2042, 4002 - 4023

  • 0.1 kW: 2056 - 2415, 4031 - 4H12

10 V: Drive capacity (motor rated power) kW

(-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-09

(0048)

Torque Reference

Shows the internal torque reference value.

0.1%

10 V = Motor rated torque (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-10

(0049)

Input Terminal Status

Shows the status of the MFDI terminal where 1 = ON, 0 = OFF.

For example, U1-10 shows “00000011” when terminals S1 and S2 are ON.

bit0
Terminal S1 (MFDI 1)
 
bit1
Terminal S2 (MFDI 2)
 
bit2
Terminal S3 (MFDI 3)
 
bit3
Terminal S4 (MFDI 4)
 
bit4
Terminal S5 (MFDI 5)
 
bit5
Terminal S6 (MFDI 6)
 
bit6
Terminal S7 (MFDI 7)
 
bit7
Terminal S8 (MFDI 8)
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-11

(004A)

Output Terminal Status

Shows the status of the MFDO terminal where 1 = ON and 0 = OFF.

For example, U1-11 shows “00000011” when terminals M1 and M3 are ON.

Note:

When H2-xx = 100 to 1A7 [Inverse Output of Function], U1-11 does not show the status in inverse.

bit0
Terminal M1-M2

Shows the status of MFDO terminals M1-M2.

bit1
Terminal M3-M4

Shows the status of MFDO terminals M3-M4.

bit2
Terminal P1-C1

Shows the status of multi-function photocoupler output 1 terminal P1-C1.

bit3
Terminal P2-C2

Shows the status of multi-function photocoupler output 2 terminal P2-C2.

bit4
Not used (normal value of 0).
 
bit5
Not used (normal value of 0).
 
bit6
Not used (normal value of 0).
 
bit7
Fault relay MA/MB-MC

Shows the status of fault relay output terminals MA/MB-MC.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-12

(004B)

Drive Status

Shows drive status where 1 = ON and 0 = OFF.

For example, U1-12 shows “00000101” during run with the Reverse Run command.

bit0
During Run
 
bit1
During zero-speed
 
bit2
During reverse
 
bit3
During fault reset signal input
 
bit4
During speed agreement
 
bit5
Drive ready
 
bit6
During minor fault detection
 
bit7
During fault detection
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-13

(004E)

Terminal A1 Level

Shows the signal level of terminal A1.

0.1%

10 V = 100% (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-14

(004F)

Terminal A2 Level

Shows the signal level of terminal A2.

0.1%

10 V = 100% (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-15

(0050)

Terminal A3 Level

Shows the signal level of terminal A3.

0.1%

10 V = 100% (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-16

(0053)

SFS Output Frequency

Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.

0.01 Hz

10 V = Maximum frequency (0 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-17

(0058)

DI-A3 Input Status

Shows the reference value input from DI-A3 option.

Shows the input signal for DI-A3 in hexadecimal as set in F3-01 [Digital Input Function Selection].

3FFFF: Set (1 bit) + Sign (1 bit) + 16 bit

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-18

(0061)

oPE Fault Parameter

Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08 [Parameter Selection Error].

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-19

(0066)

MEMOBUS/Modbus Error Code

Shows the contents of the MEMOBUS/Modbus communication error where 1 = “error” and 0 = “no error”.

For example, U1-19 shows “00000001” when there is a CRC error.

bit0
CRC Error
 
bit1
Data Length Error
 
bit2
Not used (normal value of 0).
 
bit3
Parity Error
 
bit4
Overrun Error
 
bit5
Framing Error
 
bit6
Timed Out
 
bit7
Not used (normal value of 0).
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-21

(0077)

AI-A3 Term V1 Level

Shows the analog reference of terminal V1 on analog input option card AI-A3.

0.1%

10 V = 100% (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-22

(072A)

AI-A3 Term V2 Level

Shows the analog reference of terminal V2 on analog input option card AI-A3.

0.1%

10 V = 100% (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-23

(072B)

AI-A3 Term V3 Level

Shows the analog reference of terminal V3 on analog input option card AI-A3.

0.1%

10 V = 100% (-10 V to +10 V)

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-24

(007D)

Input Pulse Monitor

Shows the frequency to pulse train input terminal RP.

1 Hz

Determined by H6-02

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-25

(004D)

SoftwareNumber Flash

Shows the FLASH ID.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-26

(005B)

SoftwareNumber ROM

Shows the ROM ID.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-50

(1199)

Expert

Virtual Analog Input

Shows the virtual analog input value.

Determined by H7-40

No.

(Hex.)

Name

Description

MFAO Signal Level

U1-91

(154E)

Expert

Output Voltage

Shows the drive internal output voltage reference.

0.1 V

200 V Class: 10 V = 200 Vrms

400 V Class: 10 V = 400 Vrms