F7: Communication Options

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-01

(03E5)

IP Address 1

Sets the first octet of the IP Address for the device that is connecting to the network. Restart the drive after you change this parameter.

Note:

When F7-13 = 0 [Address Mode at Startup = Static]:

  • Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to set a different IP address for each drive on the network.

  • Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].

192

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-02

(03E6)

IP Address 2

Sets the second octet of the IP Address for the device that is connecting to the network. Restart the drive after you change this parameter.

Note:

When F7-13 = 0 [Address Mode at Startup = Static]:

  • Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to set a different IP address for each drive on the network.

  • Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].

168

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-03

(03E7)

IP Address 3

Sets the third octet of the IP Address for the device that is connecting to the network. Restart the drive after you change this parameter.

Note:

When F7-13 = 0 [Address Mode at Startup = Static]:

  • Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to set a different IP address for each drive on the network.

  • Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].

1

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-04

(03E8)

IP Address 4

Sets the fourth octet of the IP Address for the device that is connecting to the network. Restart the drive after you change this parameter.

Note:

When F7-13 = 0 [Address Mode at Startup = Static]:

  • Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to set a different IP address for each drive on the network.

  • Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].

20

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-05

(03E9)

Subnet Mask 1

Sets the first octet of the subnet mask of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

255

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-06

(03EA)

Subnet Mask 2

Sets the second octet of the subnet mask of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

255

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-07

(03EB)

Subnet Mask 3

Sets the third octet of the subnet mask of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

255

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-08

(03EC)

Subnet Mask 4

Sets the fourth octet of the subnet mask of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

0

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-09

(03ED)

Gateway Address 1

Sets the first octet of the gateway address of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

192

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-10

(03EE)

Gateway Address 2

Sets the second octet of the gateway address of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

168

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-11

(03EF)

Gateway Address 3

Sets the third octet of the gateway address of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

1

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-12

(03F0)

Gateway Address 4

Sets the fourth octet of the gateway address of the connected network.

Note:

Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].

1

(0 - 255)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-13

(03F1)

Address Mode at Startup

Sets the method to set option card IP addresses.

0
Static
 
1
BOOTP
 
2
DHCP
 
Note:
  • The following setting values are available when using the PROFINET communication option card (SI-EP3).

    • 0: Static

    • 2: DHCP

  • When F7-13 = 0, set parameters F7-01 to F7-12 [IP Address 1 to Gateway Address 4] to set the IP Address. Be sure to set a different IP address for each drive on the network.

2

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-14

(03F2)

Duplex Mode Selection

Sets the duplex mode setting method.

0
Half/Half
 
1
Auto/Auto
 
2
Full/Full
 
3
Half/Auto

Port 1 is set to “Half” and port 2 is set to “Auto”.

4
Half/Full

Port 1 is set to “Half” and port 2 is set to “Full”.

5
Auto/Half

Port 1 is set to “Auto” and port 2 is set to “Half”.

6
Auto/Full

Port 1 is set to “Auto” and port 2 is set to “Full”.

7
Full/Half

Port 1 is set to “Full” and port 2 is set to “Half”.

8
Full/Auto

Port 1 is set to “Full” and port 2 is set to “Auto”.

1

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-15

(03F3)

Communication Speed Selection

Sets the communications speed.

10
10/10 Mbps
 
100
100/100 Mbps
 
101
10/100 Mbps
 
102
100/10 Mbps
 

10

(10, 100 - 102)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-16

(03F4)

Timeout Value

Sets the detection time for a communications timeout.

Note:

Set this parameter to 0.0 to disable the connection timeout function.

0.0 s

(0.0 - 30.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-17

(03F5)

EtherNet/IP Speed Scaling Factor

Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-18

(03F6)

EtherNet/IP Current Scale Factor

Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-19

(03F7)

EtherNet/IP Torque Scale Factor

Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-20

(03F8)

EtherNet/IP Power Scaling Factor

Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-21

(03F9)

EtherNet/IP Voltage Scale Factor

Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-22

(03FA)

EtherNet/IP Time Scaling

Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.

0

(-15 - +15)

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-23

(03FB)

Dynamic Out Param 1 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable output 1.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-24

(03FC)

Dynamic Out Param 2 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable output 2.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-25

(03FD)

Dynamic Out Param 3 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable output 3.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-26

(03FE)

Dynamic Out Param 4 for CommCard

Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set this parameter to set to configurable output 4.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-27

(03FF)

Dynamic Out Param 5 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable output 5.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-28

(0370)

Dynamic Out Param 6 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-29

(0371)

Dynamic Out Param 7 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-30

(0372)

Dynamic Out Param 8 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-31

(0373)

Dynamic Out Param 9 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

F7-32

(0374)

Dynamic Out Param 10 for CommCard

When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter. The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/Modbus address is 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-33

(0375)

Dynamic In Param 1 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set this parameter to set to configurable input 1.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-34

(0376)

Dynamic In Param 2 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set this parameter to set to configurable input 2.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-35

(0377)

Dynamic In Param 3 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set this parameter to set to configurable input 3.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-36

(0378)

Dynamic In Param 4 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set this parameter to set to configurable input 4.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-37

(0379)

Dynamic In Param 5 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set this parameter to set to configurable input 5.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-38

(037A)

Dynamic In Param 6 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-39

(037B)

Dynamic In Param 7 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-40

(037C)

Dynamic In Param 8 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-41

(037D)

Dynamic In Param 9 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-42

(037E)

Dynamic In Param 10 for CommCard

Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-60

(0780)

PZD1 Write (Control Word)

When you use a Profibus option, set the MEMOBUS/Modbus address for PZD1 (PPO output). PZD1 (PPO output) functions as the STW when F7-60 = 0 to 2.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-61

(0781)

PZD2 Write (Frequency Reference)

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO output). PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-62

(0782)

PZD3 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO output). A value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-63

(0783)

PZD4 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO output). A value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-64

(0784)

PZD5 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO output). A value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-65

(0785)

PZD6 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO output). A value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-66

(0786)

PZD7 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO output). A value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-67

(0787)

PZD8 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO output). A value of 0, 1, or 2 will disable the PZD8 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-68

(0788)

PZD9 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO output). A value of 0, 1, or 2 will disable the PZD9 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-69

(0789)

PZD10 Write

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO output). A value of 0, 1, or 2 will disable the PZD10 (PPO output) write operation to the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-70

(078A)

PZD1 Read (Status Word)

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO input). PZD1 (PPO input) functions as the ZSW when F7-70 = 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-71

(078B)

PZD2 Read (Output Frequency)

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO input). PZD2 (PPO input) functions as the HIW when F7-71 = 0.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-72

(078C)

PZD3 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO input). A value of 0 will disable the PZD3 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-73

(078D)

PZD4 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO input). A value of 0 will disable the PZD4 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-74

(078E)

PZD5 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO input). A value of 0 will disable the PZD5 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-75

(078F)

PZD6 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO input). A value of 0 will disable the PZD6 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-76

(0790)

PZD7 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO input). A value of 0 will disable the PZD7 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-77

(0791)

PZD8 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO input). A value of 0 will disable the PZD8 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-78

(0792)

PZD9 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO input). A value of 0 will disable the PZD9 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F7-79

(0793)

PZD10 Read

When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO input). A value of 0 will disable the PZD10 (PPO input) load operation from the MEMOBUS/Modbus register.

0

Details