No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-01

(050B)

Elapsed Operating Time Setting

Sets the initial value of the cumulative drive operation time in 10-hour units.

0 h

(0 - 9999 h)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-02

(050C)

Elapsed Operating Time Selection

Sets the condition that counts the cumulative operation time.

0
U4-01 Shows Total Power-up Time

Counts the time from when the drive is energized to when it is de-energized.

1
U4-01 Shows Total RUN Time

Counts the time that the drive outputs voltage.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-03

(050E)

Fan Operation Time Setting

Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.

0 h

(0 - 9999 h)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-05

(051D)

Capacitor Maintenance Setting

Sets the U4-05 [CapacitorMaintenance] monitor value.

0%

(0 - 150%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-07

(0523)

Softcharge Relay Maintenance Set

Sets the U4-06 [PreChargeRelayMainte] monitor value.

0%

(0 - 150%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-09

(0525)

IGBT Maintenance Setting

Sets the U4-07 [IGBT Maintenance] monitor value.

0%

(0 - 150%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-11

(0510)

Fault Trace/History Init (U2/U3)

Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].

0
Disabled

Keeps the records of Monitors U2-xx and U3-xx.

1
Enabled

Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-12

(0512)

kWh Monitor Initialization

Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5 Digits].

0
No Reset

Keeps the monitor values for U4-10 and U4-11.

1
Reset

Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-13

(0528)

RUN Command Counter @ Initialize

Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs (Low)], and U4-25 [Number of Runs (High)].

0
No Reset

Keeps the monitor values for U4-02, U4-24, and U4-25.

1
Reset

Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-22

(154F)

RUN

Time Format

Sets the time display format. This parameter is only available when using an LCD keypad.

0
24 Hour Clock
 
1
12 Hour Clock
 
2
12 Hour JP Clock
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-23

(1550)

RUN

Date Format

Sets the date display format. This parameter is only available when using an LCD keypad.

0
YYYY/MM/DD
 
1
DD/MM/YYYY
 
2
MM/DD/YYYY
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o4-24

(310F)

RUN

bAT Detection Selection

Sets operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM [Keypad Time Not Set].

0
Disable
 
1
Enable (Alarm Detected)
 
2
Enable (Fault Detected)
 

0

(0 - 2)

Details