No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-01

(0391)

Terminal V1 Function Selection

Sets the monitor signal (Ux-xx) output from terminal V1.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-01 = 102 to monitor U1-02 [Output Frequency].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set F4-01 = 1301 to monitor Ud-01.

102

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-02

(0392)

RUN

Terminal V1 Gain

Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output level from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-03

(0393)

Terminal V2 Function Selection

Sets the monitor signal (Ux-xx) output from terminal V2.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-03 = 103 to monitor U1-03 [Output Current].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set F4-03 = 1301 to monitor Ud-01.

103

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-04

(0394)

RUN

Terminal V2 Gain

Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal output level from terminal V2 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.

50.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-05

(0395)

RUN

Terminal V1 Bias

Sets the bias of the monitor signal that is sent from terminal V1. When an output for monitoring items is 0%, this parameter sets the analog signal output level from the V1 terminal as a percentage of 10 V or 20 mA.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-06

(0396)

RUN

Terminal V2 Bias

Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-07

(0397)

Terminal V1 Signal Level

Sets the output signal level for terminal V1.

0
0 to 10 V
 
1
-10 to 10 V
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F4-08

(0398)

Terminal V2 Signal Level

Sets the output signal level for terminal V2.

0
0 to 10 V
 
1
-10 to 10 V
 

0

(0, 1)

Details