Jump to main content

H3: Analog Inputs

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-01

(0410)

Terminal A1 Signal Level Select

Sets the input signal level for MFAI terminal A1.

0
0-10V (Lower Limit at 0)
 
1
-10 to +10V (Bipolar Reference)
 
2
4 to 20 mA
 
3
0 to 20 mA
 

0

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-02

(0434)

Terminal A1 Function Selection

Sets the function for MFAI terminal A1.

0

(0 - 32)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-03

(0411)

RUN

Terminal A1 Gain Setting

Sets the gain of the analog signal input to MFAI terminal A1.

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-04

(0412)

RUN

Terminal A1 Bias Setting

Sets the bias of the analog signal input to MFAI terminal A1.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-05

(0413)

Terminal A3 Signal Level Select

Sets the input signal level for MFAI terminal A3.

0
0-10V (Lower Limit at 0)
 
1
-10 to +10V (Bipolar Reference)
 
2
4 to 20 mA
 
3
0 to 20 mA
 

0

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-06

(0414)

Terminal A3 Function Selection

Sets the function for MFAI terminal A3.

2

(0 - 32)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-07

(0415)

RUN

Terminal A3 Gain Setting

Sets the gain of the analog signal input to MFAI terminal A3.

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-08

(0416)

RUN

Terminal A3 Bias Setting

Sets the bias of the analog signal input to MFAI terminal A3.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-09

(0417)

Terminal A2 Signal Level Select

Sets the input signal level for MFAI terminal A2.

0
0-10V (Lower Limit at 0)
 
1
-10 to +10V (Bipolar Reference)
 
2
4 to 20 mA
 
3
0 to 20 mA
 

2

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-10

(0418)

Terminal A2 Function Selection

Sets the function for MFAI terminal A2.

0

(0 - 32)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-11

(0419)

RUN

Terminal A2 Gain Setting

Sets the gain of the analog signal input to MFAI terminal A2.

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-12

(041A)

RUN

Terminal A2 Bias Setting

Sets the bias of the analog signal input to MFAI terminal A2.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-13

(041B)

Analog Input FilterTime Constant

Sets the time constant for primary delay filters on MFAI terminals.

0.03 s

(0.00 - 2.00 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-14

(041C)

Analog Input Terminal Enable Sel

Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is ON.

1
Terminal A1 only
 
2
Terminal A2 only
 
3
Terminals A1 and A2
 
4
Terminal A3 only
 
5
Terminals A1 and A3
 
6
Terminals A2 and A3
 
7
Terminals A1, A2, and A3
 

7

(1 - 7)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-16

(02F0)

Terminal A1 Offset

Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this setting.

0

(-500 - +500)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-17

(02F1)

Terminal A2 Offset

Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this setting.

0

(-500 - +500)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-18

(02F2)

Terminal A3 Offset

Sets the offset level for analog signals input to terminal A3. Usually it is not necessary to change this setting.

0

(-500 - +500)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-40

(0B5C)

Mbus Reg 15C1h Input Function

Sets the MEMOBUS AI1 function.

F

(4 - 2F)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-41

(0B5F)

Mbus Reg 15C2h Input Function

Sets the MEMOBUS AI2 function.

F

(4 - 2F)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-42

(0B62)

Mbus Reg 15C3h Input Function

Sets the MEMOBUS AI3 function.

F

(4 - 2F)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H3-43

(117F)

Mbus Reg Inputs FilterTime Const

Sets the time constant to apply a primary delay filter to the MEMOBUS analog input register values.

0.00 s

(0.00 - 2.00 s)

Details