No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-01

(0505)

LO/RE Key Function Selection

Sets the function that lets you use [LO/RE] to switch between LOCAL and REMOTE Modes.

0
Disabled

You cannot use [LO/RE] to switch between LOCAL and REMOTE Modes.

1
Enabled

You can use [LO/RE] to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL Mode is selected, [LO/RE LED] on the keypad will come on.

1

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

o2-02

(0506)

STOP Key Function Selection

Sets the function to use [STOP key] on the keypad to stop the drive when the Run command source for the drive is REMOTE (external) and not assigned to the keypad.

0
Disabled
 
1
Enabled

[STOP key] stays enabled when the Run command source has not been assigned to the keypad.

1

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-03

(0507)

User Parameter Default Value

Sets the function to keep the settings of changed parameters as user parameter defaults to use during initialization.

0
No change
 
1
Set defaults

Saves changed parameter setting values as user default settings.

2
Clear all

Deletes all of the saved user parameter setting values.

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-04

(0508)

Drive Model (KVA) Selection

Sets the Drive Model code. Set this parameter after replacing the control board.

Determined by the drive

(-)

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

o2-05

(0509)

Home Mode Freq Ref Entry Mode

Sets the function that makes it necessary to push [ENTER Key] to use the keypad to change the frequency reference value while in Drive Mode.

0
ENTER Key Required

You must push [ENTER Key] to use the keypad to change the frequency reference value.

1
Immediate / MOP-style

The frequency reference changes when you enter it with the keypad.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-06

(050A)

Keypad Disconnect Detection

Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or if you damage the cable while the keypad is the Run command source.

0
Disabled

The drive continues operation when it detects a keypad disconnection.

1
Enabled

When the drive detects a keypad disconnection, the drive detects oPr [Keypad Connection Fault], and stops operation. The motor coasts to stop.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-07

(0527)

Keypad RUN Direction @ Power-up

Sets the direction of motor rotation when the drive is energized and the keypad is the Run command source.

0
Forward
 
1
Reverse
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-09

(050D)

Reserved

-

-

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

o2-23

(11F8)

RUN

External 24V Powerloss Detection

Sets the function to give a warning if the backup external 24 V power supply turns off when the main circuit power supply is in operation.

0
Disabled

The drive does not detect the loss of the 24-V external power supply.

1
Enabled

The keypad shows the L24v [Loss of External Power 24 Supply] indicator if the drive detects the loss of the 24-V external power supply.

Note:

A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Setting Range)

Ref.

o2-24

(11FE)

LED Light Function Selection

Sets the function to show the LED status rings and keypad LED lamps.

0
Enable Status Ring & Keypad LED
 
1
LED Status Ring Disable
 
2
Keypad LED Light Disable
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-26

(1563)

Alarm Display at Ext. 24V Power

When you connect a backup external 24 V power supply, this parameter sets the function to trigger an alarm when the main circuit power supply voltage decreases.

Note:

The drive will not run when it is operating from one 24-V external power supply.

0
Disabled

The drive will not detect EP24v [External Power 24V Supply] if the main circuit power supply voltage decreases. The [Ready] light flashes quickly to identify that drive operation is not possible.

1
Enabled

The drive detects EP24v when the main circuit power supply voltage decreases.

Note:

A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-27

(1565)

bCE Detection Selection

Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth Mode.

0
Ramp to Stop
 
1
Coast to Stop
 
2
Fast Stop (Use C1-09)
 
3
Alarm Only
 
4
No Alarm Display
 

3

(0 - 4)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o2-33

(1BB6)

Expert

Initial Pole Detection (External 24 V Power Supply)

Sets initial pole detection during the first run after an external 24 V power supply energizes the main circuit. While the main circuit is energized, the drive does not do initial pole detection from the second Run command. Usually it is not necessary to change this setting.

0
Initial pole detection disabled
 
1
Initial pole detection enabled
 

1

(0, 1)

Details