No. (Hex.) Name Description Default (Range) Ref. E3-01 (0319) Motor 2 Control Mode Selection Sets the control method for motor 2. Note: When you change this setting, the drive will set all parameters that are dependent on this parameter to their default settings. 0 V/f Control 1 V/f Control with Encoder 2 Open Loop Vector 3 Closed Loop Vector 0 (0 - 3) Details No. (Hex.) Name Description Default (Range) Ref. E3-04 (031A) Motor 2 Maximum Output Frequency Set the maximum output frequency for the motor 2 V/f pattern. Determined by E3-01 (40.0 - 590.0 Hz) Details No. (Hex.) Name Description Default (Range) Ref. E3-05 (031B) Motor 2 Maximum Output Voltage Sets the maximum output voltage for the motor 2 V/f pattern. Determined by E3-01 (200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V) Details No. (Hex.) Name Description Default (Range) Ref. E3-06 (031C) Motor 2 Base Frequency Sets the base frequency for the motor 2 V/f pattern. Determined by E3-01 (0.0 - E3-04) Details No. (Hex.) Name Description Default (Range) Ref. E3-07 (031D) Motor 2 Mid Point A Frequency Sets a middle output frequency for the motor 2 V/f pattern. Determined by E3-01 (0.0 - E3-04) Details No. (Hex.) Name Description Default (Range) Ref. E3-08 (031E) Motor 2 Mid Point A Voltage Sets a middle output voltage for the motor 2 V/f pattern. Determined by E3-01 (200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V) Details No. (Hex.) Name Description Default (Range) Ref. E3-09 (031F) Motor 2 Minimum Output Frequency Sets the minimum output frequency for the motor 2 V/f pattern. Determined by E3-01 (0.0 - E3-04) Details No. (Hex.) Name Description Default (Range) Ref. E3-10 (0320) Motor 2 Minimum Output Voltage Sets the minimum output voltage for the motor 2 V/f pattern. Determined by E3-01 (200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V) Details No. (Hex.) Name Description Default (Range) Ref. E3-11 (0345) Expert Motor 2 Mid Point B Frequency Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter. 0.0 Hz (0.0 - E3-04) Details No. (Hex.) Name Description Default (Range) Ref. E3-12 (0346) Expert Motor 2 Mid Point B Voltage Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter. 0.0 V (200 V Class: 0.0 to 255.0 V, 400 V Class: 0.0 to 510.0 V) Details No. (Hex.) Name Description Default (Range) Ref. E3-13 (0347) Expert Motor 2 Base Voltage Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter. 0.0 V (200 V Class: 0.0 to 255.0 V, 400 V Class: 0.0 to 510.0 V) Details