No. (Hex.) Name Description Default (Range) Ref. d6-01 (02A0) Field Weakening Level Sets the drive output voltage as a percentage of E1-05 [Maximum Output Voltage] when H1-xx = 63 [Field Weakening] is activated. 80% (0 - 100%) Details No. (Hex.) Name Description Default (Range) Ref. d6-02 (02A1) Field Weakening Frequency Limit Sets the minimum output frequency to start field weakening. 0.0 Hz (0.0 - 590.0 Hz) Details No. (Hex.) Name Description Default (Range) Ref. d6-03 (02A2) Field Forcing Selection Sets the field forcing function. 0 Disabled 1 Enabled 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. d6-06 (02A5) Field Forcing Limit Sets the limit value for field forcing to increase the motor excitation current reference as a percentage of E2-03 [Motor No-Load Current]. Usually it is not necessary to change this setting. 400% (100 - 400%) Details