Setting Value

Function

Description

Ref.

0

Frequency Reference

The input value from the MFAI terminal set with this function becomes the master frequency reference.

Details

Setting Value

Function

Description

Ref.

1

Frequency Gain

The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.

Details

Setting Value

Function

Description

Ref.

2

Auxiliary Frequency Reference 1

Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference 1) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is a setting value of 100%.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

3

Auxiliary Frequency Reference 2

Sets Reference 3 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference 2) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is a setting value of 100%.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

4

Output Voltage Bias

Set this parameter to input a bias signal and amplify the output voltage.

Details

Setting Value

Function

Description

Ref.

5

Accel/Decel Time Gain

Enters a signal to adjust the gain used for C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4] and C1-09 [Fast Stop Time] when the full scale analog signal (10 V or 20 mA) is 100%.

Details

Setting Value

Function

Description

Ref.

6

DC Injection Braking Current

Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.

Details

Setting Value

Function

Description

Ref.

7

Torque Detection Level

Enters a signal to adjust the overtorque/undertorque detection level.

Note:

Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02 [Torque Detection Level 1].

Details

Setting Value

Function

Description

Ref.

8

Stall Prevent Level During Run

Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.

Details

Setting Value

Function

Description

Ref.

9

Output Frequency Lower Limit

Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

B

PID Feedback

Enter the PID feedback value as a percentage of the maximum output frequency.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

C

PID Setpoint

Enters the PID setpoint as a percentage of the maximum output frequency.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

D

Frequency Bias

Enters the bias value added to the frequency reference as a percentage of the maximum output frequency.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

Details

Setting Value

Function

Description

Ref.

E

Motor Temperature (PTC Input)

Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage of the current value when the 10 V analog signal is input.

Details

Setting Value

Function

Description

Ref.

F

Not Used

Use this setting for unused terminals or to use terminals in through mode.

Details

Setting Value

Function

Description

Ref.

10

Forward Torque Limit

Enters the forward torque limit if the motor rated torque is 100%.

Details

Setting Value

Function

Description

Ref.

11

Reverse Torque Limit

Enters the load torque limit if the motor rated torque is 100%.

Details

Setting Value

Function

Description

Ref.

12

Regenerative Torque Limit

Enters the regenerative torque limit if the motor rated torque is 100%.

Details

Setting Value

Function

Description

Ref.

13

Torque Reference / Torque Limit

Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for speed control.

Details

Setting Value

Function

Description

Ref.

14

Torque Compensation

Enters the torque compensation value if the motor rated torque is 100%.

Details

Setting Value

Function

Description

Ref.

15

General Torque Limit

Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor rated torque is 100%.

Details

Setting Value

Function

Description

Ref.

16

Differential PID Feedback

Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.

Details

Setting Value

Function

Description

Ref.

17

Expert

Motor Temperature (NTC Input)

Set this parameter when you connect the motor thermistor. Detects the motor temperature and protects the motor.

Note:

When A1-02 = 3 [Control Method Selection = CLV], motor protection and compensation for slip caused by motor temperature is possible.

Details

Setting Value

Function

Description

Ref.

1F

Not Used

Use this setting for unused terminals or to use terminals in through mode.

Details

Setting Value

Function

Description

Ref.

30

DWEZ Analog Input 1

Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

31

DWEZ Analog Input 2

Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

32

DWEZ Analog Input 3

Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.

Details