H2-xx: MFDO Setting Values

Setting Value

Function

Description

Ref.

0

During Run

The terminal activates when you input a Run command and when the drive is outputting voltage.

ON
Drive is running

The drive is receiving a Run command or outputting voltage.

OFF
Drive is stopping
 

Details

Setting Value

Function

Description

Ref.

1

Zero Speed

The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero SpeedThreshold].

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the reference.

 

A1-02 Setting

Control method selection

Parameter Used as the Reference

0

V/f

E1-09

1

CL-V/f

E1-09

2

OLV

b2-01

3

CLV

E1-09

4

AOLV

E1-09

5

OLV/PM

E1-09

6

AOLV/PM

E1-09

7

CLV/PM

b2-01

8

EZOLV

E1-09

ON
Output frequency < value of E1-09 or b2-01.
 
OFF
Output frequency ≥ value of E1-09 or b2-01.
 

Details

Setting Value

Function

Description

Ref.

2

Speed Agree 1

The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].

Note:
  • The detection function operates in the two motor rotation directions.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-72 = 1.

ON
The output frequency is in the range of “frequency reference ± L4-02”.
 
OFF
The output frequency does not align with the frequency reference although the drive is running.
 

Details

Setting Value

Function

Description

Ref.

3

User-Set Speed Agree 1

The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.

Note:
  • The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-72 = 1.

ON
The output frequency is in the range of “L4-01 ± L4-02” and the range of frequency reference ± L4-02.
 
OFF
The output frequency is not in the range of “L4-01 ± L4-02” or the range of frequency reference ± L4-02.
 

Details

Setting Value

Function

Description

Ref.

4

Frequency Detection 1

The terminal deactivates when the output frequency > “L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection Width]”. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of L4-01.

Note:
  • The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With Encoder].

ON
The output frequency < L4-01, or the output frequency ≤ “L4-01 + L4-02
 
OFF
The output frequency > “L4-01 + L4-02
 

Details

Setting Value

Function

Description

Ref.

5

Frequency Detection 2

The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal activates, the terminal stays activated until the output frequency is at the value of “L4-01 - L4-02”.

Note:
  • The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With Encoder].

ON
The output frequency > L4-01
 
OFF
The output frequency < “L4-01 - L4-02”, or the output frequency ≤ L4-01
 

Details

Setting Value

Function

Description

Ref.

6

Drive Ready

The terminal activates when the drive is ready and running.

Details

Setting Value

Function

Description

Ref.

7

DC Bus Undervoltage

The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in L2-05 [Undervoltage Detection Lvl (Uv1)] or less. The terminal also activates when there is a fault with the DC bus voltage.

ON
The DC bus voltage ≤ L2-05
 
OFF
The DC bus voltage > L2-05
 

Details

Setting Value

Function

Description

Ref.

8

During Baseblock (N.O.)

The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not make DC bus voltage.

ON
During baseblock
 
OFF
The drive is not in baseblock.
 

Details

Setting Value

Function

Description

Ref.

9

Frequency Reference from Keypad

Shows the selected frequency reference source.

ON
The keypad is the frequency reference source.
 
OFF
Parameter b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
 

Details

Setting Value

Function

Description

Ref.

A

Run Command Source

Shows the selected Run command source.

ON
The keypad is the Run command source.
 
OFF
Parameter b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
 

Details

Setting Value

Function

Description

Ref.

B

Torque Detection 1 (N.O.)

The terminal activates when the drive detects overtorque or undertorque.

ON
The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
 

Details

Setting Value

Function

Description

Ref.

C

Frequency Reference Loss

The terminal activates when the drive detects a loss of frequency reference.

Details

Setting Value

Function

Description

Ref.

D

Braking Resistor Fault

The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.

Details

Setting Value

Function

Description

Ref.

E

Fault

The terminal activates when the drive detects a fault.

Note:

The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.

Details

Setting Value

Function

Description

Ref.

F

Not Used

Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.

Details

Setting Value

Function

Description

Ref.

10

Alarm

The terminal activates when the drive detects a minor fault.

Details

Setting Value

Function

Description

Ref.

11

Fault Reset Command Active

The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the communication option.

Details

Setting Value

Function

Description

Ref.

12

Timer Output

Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 18 [MFDI Function Selection = Timer Function].

Details

Setting Value

Function

Description

Ref.

13

Speed Agree 2

The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width (+/-)].

Note:
  • The detection function operates in the two motor rotation directions.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].

ON
The output frequency is in the range of “frequency reference ± L4-04”.
 
OFF
The output frequency is not in the range of “frequency reference ± L4-04”.
 

Details

Setting Value

Function

Description

Ref.

14

User-Set Speed Agree 2

The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.

Note:
  • The detection level set in L4-03 is a signed value. The drive will only detect in one direction.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].

ON
The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency reference ± L4-04.
 
OFF
The output frequency is not in the range of “L4-03 ± L4-04” or the range of frequency reference ± L4-04.
 

Details

Setting Value

Function

Description

Ref.

15

Frequency Detection 3

The terminal deactivates when the output frequency > “L4-03 [Speed Agree Detection Level(+/-)] + L4-04 [Speed Agree Detection Width(+/-)]”. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of L4-03.

Note:
  • The detection level set in L4-03 is a signed value. The drive will only detect in one direction.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].

ON
The output frequency < L4-03, or the output frequency ≤ “L4-03 + L4-04
 
OFF
The output frequency > “L4-03 + L4-04
 

Details

Setting Value

Function

Description

Ref.

16

Frequency Detection 4

The terminal activates when the output frequency > L4-03 [Speed Agree Detection Level(+/-)]. After the terminal activates, the terminal stays activated until the output frequency is at the value of “L4-03 - L4-04”.

Note:
  • The detection level set in L4-03 is a signed value. The drive will only detect in one direction.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].

ON
The output frequency > L4-03
 
OFF
The output frequency < “L4-03 - L4-04”, or the output frequency ≤ L4-03
 

Details

Setting Value

Function

Description

Ref.

17

Torque Detection 1 (N.C.)

The terminal deactivates when the drive detects overtorque or undertorque.

OFF
The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
 

Details

Setting Value

Function

Description

Ref.

18

Torque Detection 2 (N.O.)

The terminal activates when the drive detects overtorque or undertorque.

ON
The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer than the time set in L6-06 [Torque Detection Time 2].
 

Details

Setting Value

Function

Description

Ref.

19

Torque Detection 2 (N.C.)

The terminal deactivates when the drive detects overtorque or undertorque.

OFF
The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer than the time set in L6-06 [Torque Detection Time 2].
 

Details

Setting Value

Function

Description

Ref.

1A

During Reverse

The terminal activates when the motor operates in the reverse direction.

ON
The motor is operating in the reverse direction.
 
OFF
The motor is operating in the forward direction or the motor stopped.
 

Details

Setting Value

Function

Description

Ref.

1B

During Baseblock (N.C.)

The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not make DC bus voltage.

ON
The drive is not in baseblock.
 
OFF
During baseblock
 

Details

Setting Value

Function

Description

Ref.

1C

Motor 2 Selected

The terminal activates when you select motor 2.

ON
Motor 2 Selected
 
OFF
Motor 1 Selected
 

Details

Setting Value

Function

Description

Ref.

1D

During Regeneration

The terminal activates on when the motor is regenerating.

ON
Motor is regenerating.
 
OFF
Motor is operating or stopped.
 

Details

Setting Value

Function

Description

Ref.

1E

Executing Auto-Restart

The terminal activates when the Auto Restart function is trying to restart after a fault.

Details

Setting Value

Function

Description

Ref.

1F

Motor Overload Alarm (oL1)

The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of 90% of the detection level.

Details

Setting Value

Function

Description

Ref.

20

Drive Overheat Pre-Alarm (oH)

The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].

Details

Setting Value

Function

Description

Ref.

21

Safety Monitor Output Status

The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when terminals H1-HC and H2-HC are OFF (Open).

ON
Safety stop state
 
OFF
Safety circuit fault or RUN/READY
 

Details

Setting Value

Function

Description

Ref.

22

Mechanical Weakening Detection

The terminal activates when the drive detects mechanical weakening.

Details

Setting Value

Function

Description

Ref.

2F

Maintenance Notification

The terminal activates when drive components are at their estimated maintenance period.

Tells you about the maintenance period for these items:

  • IGBT

  • Cooling Fan

  • Capacitor

  • Soft charge bypass relay

Details

Setting Value

Function

Description

Ref.

30

During Torque Limit

The terminal activates when the torque reference is the torque limit set with L7 parameters, H3-02, H3-06, or H3-10 [MFAI Function Selection].

Details

Setting Value

Function

Description

Ref.

31

During Speed Limit

The terminal activates when the speed limit is active.

Details

Setting Value

Function

Description

Ref.

32

In Speed Limit During Trq Ctrl

The motor accelerates in the forward direction or the reverse direction after enabling torque control and the externally input torque reference is disproportionate to the load. The output terminal activates when this speed is not higher than a constant speed and the motor speed is at the speed limit. This does not include operation when the drive is stopped.

Details

Setting Value

Function

Description

Ref.

33

Zero Servo Complete

The terminal activates when positioning in the range set with b9-02 [Zero Servo Completion Window] completes after sending the Zero-Servo command.

Details

Setting Value

Function

Description

Ref.

37

During Frequency Output

The terminal activates when the drive outputs frequency.

ON
The drive is outputting frequency.
 
OFF
The drive is not outputting frequency.
 

Details

Setting Value

Function

Description

Ref.

38

Drive Enabled

This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.

Details

Setting Value

Function

Description

Ref.

39

Watt Hour Pulse Output

Outputs the pulse that shows the watt hours.

Details

Setting Value

Function

Description

Ref.

3C

LOCAL Control Selected

The terminal activates when the Run command source or frequency reference source is LOCAL.

ON
LOCAL

The keypad is the Run command source or the frequency reference source.

OFF
REMOTE

The Run command source or frequency reference source is an external source set with b1-01 [Frequency Reference Selection 1], b1-15 [Frequency Reference Selection 2], b1-02 [Run Command Selection 1], or b1-16 [Run Command Selection 2].

Details

Setting Value

Function

Description

Ref.

3D

During Speed Search

The terminal activates when the drive is doing speed search.

Details

Setting Value

Function

Description

Ref.

3E

PID Feedback Low

The terminal activates when the drive detects FbL [PID Feedback Loss].

Details

Setting Value

Function

Description

Ref.

3F

PID Feedback High

The terminal activates when the drive detects FbH [Excessive PID Feedback].

Details

Setting Value

Function

Description

Ref.

4 A

During KEB Ride-Thru

The activates during KEB Ride-Thru.

Details

Setting Value

Function

Description

Ref.

4B

During Short Circuit Braking

The terminal activates during Short Circuit Braking.

Note:

When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.

Details

Setting Value

Function

Description

Ref.

4C

During Fast Stop

The terminal activates when the fast stop is in operation.

Details

Setting Value

Function

Description

Ref.

4D

oH Pre-Alarm Time Limit

The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH [Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.

Details

Setting Value

Function

Description

Ref.

4E

Braking Transistor Fault (rr)

The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor Fault] fault.

Details

Setting Value

Function

Description

Ref.

4F

Braking Resistor Overheat (rH)

The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat] fault.

Details

Setting Value

Function

Description

Ref.

60

Internal Cooling Fan Failure

The terminal activates when the drive detects a cooling fan failure in the drive.

Details

Setting Value

Function

Description

Ref.

61

Pole Position Detection Complete

The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.

Details

Setting Value

Function

Description

Ref.

62

Modbus Reg 1 Status Satisfied

The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register address set with H2-07 [Modbus Register 1 Address Select] activates.

Details

Setting Value

Function

Description

Ref.

63

Modbus Reg 2 Status Satisfied

The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register address set with H2-09 [Modbus Register 2 Address Select] activates.

Details

Setting Value

Function

Description

Ref.

65

Standby Output

The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].

ON
The Run command turns on and the magnetic contactor on the input side turns on.
 
OFF
The Run command turns off and the drive stops operating. Then, the magnetic contactor on the input side turns off after the time set in b8-51 [Standby Mode Wait Time]elapses.
 

Details

Setting Value

Function

Description

Ref.

66

Comparator1

The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator 1 On-Delay Time].

Details

Setting Value

Function

Description

Ref.

67

Comparator2

The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30 [Comparator 2 On-Delay Time].

Details

Setting Value

Function

Description

Ref.

69

External Power 24V Supply

The terminal activates when there is an external 24V power supply between terminals PS-AC.

ON
The external 24V power supply is supplying power.
 
OFF
The external 24V power supply is not supplying power.
 

Details

Setting Value

Function

Description

Ref.

6 A

Data Logger Error

The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].

Details

Setting Value

Function

Description

Ref.

90

DWEZ Digital Output 1

Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

91

DWEZ Digital Output 2

Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

92

DWEZ Digital Output 3

Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

93

DWEZ Digital Output 4

Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A0

DWEZ Extended Digital Output 1

Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A1

DWEZ Extended Digital Output 2

Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A2

DWEZ Extended Digital Output 3

Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A3

DWEZ Extended Digital Output 4

Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A4

DWEZ Extended Digital Output 5

Sets the DriveWorksEZ digital output 5. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A5

DWEZ Extended Digital Output 6

Sets the DriveWorksEZ digital output 6. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A6

DWEZ Extended Digital Output 7

Sets the DriveWorksEZ digital output 7. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

A7

DWEZ Extended Digital Output 8

Sets the DriveWorksEZ digital output 8. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

100

!During Run

The terminal deactivates when you input a Run command and when the drive is outputting voltage.

ON
Drive is stopping
 
OFF
Drive is running

The drive is receiving a Run command, or the drive is decelerating or during a DC Injection Braking.

Details

Setting Value

Function

Description

Ref.

101

!Zero Speed

The terminal deactivates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero SpeedThreshold].

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the reference.

 

A1-02 Setting

Description

Parameter Used as the Reference

0

Open Loop V/f Control

E1-09

1

V/f Control with Encoder

E1-09

2

Open Loop Vector

b2-01

3

Closed Loop Vector

E1-09

4

Advanced OpenLoop Vector Control

E1-09

5

PM Open Loop Vector Control

E1-09

6

PM Advanced Open Loop Vector

E1-09

7

PM Closed Loop Vector Control

b2-01

8

EZ Open Loop Vector Control

E1-09

ON
The output frequency is the value of E1-09 or more, or b2-01 or more.
 
OFF
The output frequency is less than the value of E1-09 or b2-01.
 

Details

Setting Value

Function

Description

Ref.

102

!Speed Agree 1

The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].

Note:

In CLV, the motor speed is the reference.

ON
The output frequency does not align with the frequency reference although the drive is running.
 
OFF
The output frequency is in the range of “frequency reference ± L4-02”.
 

Details

Setting Value

Function

Description

Ref.

103

!User-Set Speed Agree 1

The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.

Note:
  • The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.

  • When using Closed Loop Vector Control, this is the value of “Motor Speed ± L4-02.”

ON
The output frequency is not in the range of “L4-01 ± L4-02” nor the range of frequency reference ± L4-02.
 
OFF
The output frequency is in the range of “L4-01 ± L4-02” and the range of frequency reference ± L4-02.
 

Details

Setting Value

Function

Description

Ref.

104

!Frequency Detection 1

The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection Width]. When the terminal activates, it stays activated until the output frequency = L4-01.

Note:
  • The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.

  • In CLV, the motor speed is the reference.

ON
The output frequency is higher than L4-01 + L4-02.
 
OFF
The output frequency is less than L4-01 or is not more than L4-01 + L4-02.
 

Details

Setting Value

Function

Description

Ref.

105

!Frequency Detection 2

The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level]. When the terminal deactivates, it stays deactivated until the output frequency = L4-01 - L4-02.

ON
The output frequency is less than “L4-01 - L4-02,” or it is not more than L4-01.
 
OFF
The output frequency is more than L4-01.
 

Details

Setting Value

Function

Description

Ref.

106

!Drive Ready

The terminal deactivates when the drive is ready and running.

Details

Setting Value

Function

Description

Ref.

107

!DC Bus Undervoltage

The terminal deactivates when the DC bus voltage or control circuit power supply is at or below the voltage set in L2-05 [Undervoltage Detection Lvl (Uv1)]. The terminal also deactivates when there is a fault with the DC bus voltage.

ON
The DC bus voltage is more than the setting value of L2-05.
 
OFF
The DC bus voltage is less than the setting value of L2-05.
 

Details

Setting Value

Function

Description

Ref.

108

During Baseblock (N.C.)

The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not make DC bus voltage.

ON
The drive is not in baseblock.
 
OFF
During baseblock
 

Details

Setting Value

Function

Description

Ref.

109

!Frequency Reference from Keypad

Shows the selected frequency reference source.

ON
b1-01 [Frequency Reference Selection 1] or b1-15 [Frequency Reference Selection 2] is the frequency reference source.
 
OFF
The keypad is the frequency reference source.
 

Details

Setting Value

Function

Description

Ref.

10A

!Run Command from Keypad

Shows the selected Run command source.

ON
b1-02 [Run Command Selection 1] or b1-16 [Run Command Selection 2] is the Run command source.
 
OFF
The keypad is the Run command source.
 

Details

Setting Value

Function

Description

Ref.

10B

Torque Detection 1 (N.C.)

The terminal deactivates when the drive detects overtorque or undertorque.

OFF
The output current/torque exceeds the torque value set with L6-02 [Torque Detection Level 1], or the level has dropped and remained in this state longer than the time set with L6-03 [Torque Detection Time 1].
 

Details

Setting Value

Function

Description

Ref.

10C

!Frequency Reference Loss

The terminal deactivates when the drive detects a loss of frequency reference.

Details

Setting Value

Function

Description

Ref.

10D

!Braking Resistor Fault

The terminal deactivates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.

Details

Setting Value

Function

Description

Ref.

10E

!Fault

The terminal deactivates when the drive detects a fault.

Note:

Faults CPF00 and CPF01 [Control Circuit Error] are excluded.

Details

Setting Value

Function

Description

Ref.

110

!Alarm

The terminal deactivates when the drive detects a minor fault.

Details

Setting Value

Function

Description

Ref.

111

!Fault Reset Command Active

The terminal deactivates when the drive receives the Reset command from the control circuit terminal, serial communications, or the communication option.

Details

Setting Value

Function

Description

Ref.

112

!Timer Output

Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 118 [MFDI Function Selection = !Timer Function].

Details

Setting Value

Function

Description

Ref.

113

!Speed Agree 2

The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width(+/-)].

Note:

The drive uses the motor speed as the reference in CLV and CLV/PM.

ON
The output frequency is not in the range of “frequency reference ± L4-04”.
 
OFF
The output frequency is in the range of “frequency reference ± L4-04”.
 

Details

Setting Value

Function

Description

Ref.

114

!User-Set Speed Agree 2

The terminal deactivates when the output frequency is in the range of L4-03 [Speed Agree Detection Level(+/-)] ± L4-04 [Speed Agree Detection Width(+/-)] and in the range of the frequency reference ± L4-04.

ON
The output frequency is not in the range of “L4-03 ± L4-04” nor the range of frequency reference ± L4-04.
 
OFF
The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency reference ± L4-04.
 

Details

Setting Value

Function

Description

Ref.

115

!Frequency Detection 3

The terminal activates when the output frequency is higher than “L4-03 [Speed Agree Detection Level(+/-)] + L4-04 [Speed Agree Detection Width(+/-)]”. When the terminal activates, it stays activated until the output frequency = L4-03.

Note:
  • The detection level set in L4-03 is a signed value. Detections only occur one specific orientation.

  • The drive uses the motor speed as the reference in CLV and CLV/PM.

ON
The output frequency is higher than L4-03 + L4-04.
 
OFF
The output frequency is less than L4-03 or is not more than L4-03 + L4-04.
 

Details

Setting Value

Function

Description

Ref.

116

!Frequency Detection 4

The terminal deactivates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level(+/-)]. After the terminal deactivates, the terminal stays deactivated until the output frequency = L4-03 - L4-04.

ON
The output frequency is less than “L4-03 - L4-04,” or it is not more than L4-03.
 
OFF
The output frequency is more than L4-03.
 

Details

Setting Value

Function

Description

Ref.

117

Torque Detection 1 (N.O.)

The terminal activates when the drive detects overtorque or undertorque.

ON
The output current/torque exceeds the torque value set with L6-02 [Torque Detection Level 1], or the level has dropped and remained in this state longer than the time set with L6-03 [Torque Detection Time 1].
 

Details

Setting Value

Function

Description

Ref.

118

Torque Detection 2 (N.C.)

The terminal deactivates when the drive detects overtorque or undertorque.

OFF
The output current/torque exceeds the torque value set with L6-05 [Torque Detection Level 2], or the level has dropped and remained in this state longer than the time set with L6-06 [Torque Detection Time 2].
 

Details

Setting Value

Function

Description

Ref.

119

Torque Detection 2 (N.O.)

The terminal activates when the drive detects overtorque or undertorque.

ON
The output current/torque exceeds the torque value set with L6-05 [Torque Detection Level 2], or the level has dropped and remained in this state longer than the time set with L6-06 [Torque Detection Time 2].
 

Details

Setting Value

Function

Description

Ref.

11A

!During Reverse

The terminal deactivates when the motor operates in the reverse direction.

ON
The motor is operating in the forward direction or the motor stopped.
 
OFF
The motor is operating in the reverse direction.
 

Details

Setting Value

Function

Description

Ref.

11B

During Baseblock (N.O.)

The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not make DC bus voltage.

ON
During baseblock
 
OFF
The drive is not in baseblock.
 

Details

Setting Value

Function

Description

Ref.

11C

!Motor 2 Selected

The terminal deactivates when motor 2 is selected.

ON
Motor 1 Selection
 
OFF
Motor 2 Selection
 

Details

Setting Value

Function

Description

Ref.

11D

!During Regeneration

The terminal deactivates when the motor is regenerating.

ON
Motor is operating or stopped.
 
OFF
Motor is regenerating.
 

Details

Setting Value

Function

Description

Ref.

11E

!Executing Auto-Restart

The terminal deactivates when the Auto Restart function is trying to restart after a fault.

Details

Setting Value

Function

Description

Ref.

11F

!Motor Overload Alarm (oL1)

The terminal deactivates when the electronic thermal protection value of the motor overload protective function is a minimum of 90% of the detection level.

Details

Setting Value

Function

Description

Ref.

120

!Drive Overheat Pre-Alarm (oH)

The terminal deactivates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].

Details

Setting Value

Function

Description

Ref.

121

!Safe Torque OFF

The terminal deactivates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when terminals H1-HC and H2-HC are OFF (Open).

ON
Safety circuit fault or RUN/READY
 
OFF
Safety stop state
 

Details

Setting Value

Function

Description

Ref.

122

!Mechanical Weakening Detection

The terminal deactivates when the drive detects mechanical weakening.

Details

Setting Value

Function

Description

Ref.

12F

!Maintenance Notification

The terminal deactivates when drive components are at their estimated maintenance period.

Tells you about the maintenance period for these items:

  • IGBT

  • Cooling Fan

  • Capacitor

  • Soft charge bypass relay

Details

Setting Value

Function

Description

Ref.

130

!During Torque Limit

The terminal deactivates when the torque reference is the torque limit set with L7 parameters, H3-02, H3-06, or H3-10 [MFAI Function Selection].

Details

Setting Value

Function

Description

Ref.

131

!During Speed Limit

The terminal deactivates when the speed limit is active.

Details

Setting Value

Function

Description

Ref.

132

!In Speed Limit During Trq Ctrl

The motor accelerates in the forward direction or the reverse direction after enabling torque control and the externally-input torque reference is disproportionate to the load. The output terminal deactivates when this speed is not higher than a constant speed and the motor speed is at the speed limit. This does not include operation when the drive is stopped.

Details

Setting Value

Function

Description

Ref.

133

!Zero Servo Complete

The terminal deactivates when positioning in the range set with b9-02 [Zero Servo Completion Window] completes after sending the Zero-Servo command.

Details

Setting Value

Function

Description

Ref.

137

!During Frequency Output

The terminal deactivates when the drive outputs frequency.

ON
The drive is not outputting frequency.
 
OFF
The drive is outputting frequency.
 

Details

Setting Value

Function

Description

Ref.

138

!Drive Enabled

This terminal deactivates when the H1-xx = 16A [Drive Enable] terminal deactivates.

Details

Setting Value

Function

Description

Ref.

139

!Watt Hour Pulse Output

Outputs the pulse that shows the watt hours.

Details

Setting Value

Function

Description

Ref.

13C

!LOCAL Control Selected

The terminal deactivates when the Run command source or frequency reference source is LOCAL.

ON
REMOTE

The Run command source or frequency reference source is an external source selected with b1-01 [Frequency Reference Selection 1], b1-15 [Frequency Reference Selection 2], b1-02 [Run Command Selection 1], or b1-16 [Run Command Selection 2].

OFF
LOCAL

The keypad is the Run command source or the frequency reference source.

Details

Setting Value

Function

Description

Ref.

13D

!During Speed Search

The terminal deactivates when the drive does speed search.

Details

Setting Value

Function

Description

Ref.

13E

!PID Feedback Low

The terminal deactivates when the drive detects FbL [PID Feedback Loss].

Details

Setting Value

Function

Description

Ref.

13F

!PID Feedback High

The terminal deactivates when the drive detects FbH [Excessive PID Feedback].

Details

Setting Value

Function

Description

Ref.

14A

!During KEB Ride-Thru

The terminal deactivates when the drive executes the KEB Ride-Thru function.

Details

Setting Value

Function

Description

Ref.

14B

!During Short Circuit Braking

The terminal deactivates during Short Circuit Braking.

Note:

When A1-02 = 8 [Control Method Selection = EZ Vector Control], this function is available when you use a PM motor.

Details

Setting Value

Function

Description

Ref.

14C

!During Fast Stop

The terminal deactivates when the fast stop is in operation.

Details

Setting Value

Function

Description

Ref.

14D

!oH Pre-Alarm Reduction Limit

The terminal deactivates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH [Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.

Details

Setting Value

Function

Description

Ref.

14E

!Braking Transistor Fault (rr)

The terminal deactivates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor Fault] fault.

Details

Setting Value

Function

Description

Ref.

14F

!Braking Resistor Overheat (rH)

The terminal deactivates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat] fault.

Details

Setting Value

Function

Description

Ref.

160

!Internal Cooling Fan Failure

The terminal deactivates when the drive detects a cooling fan failure in the drive.

Details

Setting Value

Function

Description

Ref.

161

!RotorPositionDetection Complete

The terminal deactivates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.

Details

Setting Value

Function

Description

Ref.

162

!Modbus Reg 1 Status Satisfied

The terminal deactivates when the bit specified by H2-07 turns on regarding the MEMOBUS register address configured with H2-08.

Details

Setting Value

Function

Description

Ref.

163

!Modbus Reg 2 Status Satisfied

The terminal deactivates when the bit specified by H2-10 turns on regarding the MEMOBUS register address configured with H2-09.

Details

Setting Value

Function

Description

Ref.

165

!Standby Output

The terminal activated after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].

ON
The Run command turns off and the drive stops operating. When time set in b8-51 [Standby Mode Wait Time] is expired, the magnetic contactor on the input side turns off.
 
OFF
The Run command turns on and the magnetic contactor on the input side turns on.
 

Details

Setting Value

Function

Description

Ref.

166

!Comparator 1

The terminal deactivates when the monitor value set with H2-20 is within range of H2-21 and H2-22 for the time set in H2-24.

Details

Setting Value

Function

Description

Ref.

167

!Comparator 2

The terminal deactivates when the when the monitor value set with H2-26 is outside the range of H2-27 and H2-28 for the time set in H2-30.

Details

Setting Value

Function

Description

Ref.

169

!External Power 24V Supply

The terminal deactivates when there is an external 24V power supply between terminals PS-AC.

ON
The external 24V power supply is not supplying power.
 
OFF
The external 24V power supply is supplying power.
 

Details

Setting Value

Function

Description

Ref.

16A

!Data Logger Error

The terminal deactivates when the drive detects a LoG [Com Error / Abnormal SD card].

Details

Setting Value

Function

Description

Ref.

190

!DWEZ Digital Output 1

Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

191

!DWEZ Digital Output 2

Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

192

!DWEZ Digital Output 3

Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

193

!DWEZ Digital Output 4

Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A0

!DWEZ Extended Digital Output 1

Sets the digital output 1 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A1

!DWEZ Extended Digital Output 2

Sets the digital output 2 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A2

!DWEZ Extended Digital Output 3

Sets the digital output 3 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A3

!DWEZ Extended Digital Output 4

Sets the digital output 4 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A4

!DWEZ Extended Digital Output 5

Sets the digital output 5 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A5

!DWEZ Extended Digital Output 6

Sets the digital output 6 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A6

!DWEZ Extended Digital Output 7

Sets the digital output 7 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details

Setting Value

Function

Description

Ref.

1A7

!DWEZ Extended Digital Output 8

Sets the digital output 8 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more information.

Details